Case Study: Clean Rooms For International Pharmaceutical Company

Penmann were contracted to design, supply and install the plant to serve a new Pharmaceutical Aseptic Filling Suite.

The Suite comprised a Grade C (Class 10,000) environment for preparation rooms, air locks and change areas, and a Grade B (Class 1,000 operating) environment for the assembly area with a localized Grade A (Class 100) area within assembly area.



The Suite was designed with a cascading air pressure design ranging from 45Pa in the assembly area down to 0Pa in the dirty corridor. The pressure balance had to be maintained with a variety of equipment operating conditions which affected exhaust volumes from the area and leakage rates through machinery straddling boundaries.

There was also a requirement to allow the assembly area to drop to a set back pressure, lower than adjacent areas, during maintenance modes.

HEPA filtration was provided to H14 classification utilizing factory assembled disposable ceiling terminals.

Constant air volumes were maintained by a combination of frequency inverters control of the fans and in duct constant volume devices to compensate as filters start to block and reduce air flow

A 9m² Grade A environment was provided adjacent to the autoclave serving the assembly area utilizing a laminar flow canopy and polycarbonate partition.

The plant was fully commissioned and validated on completion, including provision of all necessary qualification documentation.

Key Features

  • Pressure cascade
  • Secondary pressure option for maintenance mode
  • Self regulating pressure stabilizers
  • Pressure maintained over high range of machinery exhaust volumes

<< Overview Next Case Study >>


Brochure Download Download our latest brochure here in Adobe PDF format
Click here to Download

Automotive

How to control the temperature in a Dynamometer Test Facility to operate at any point between +40ºC and -10ºC.

Displacement

Helps reduce problem with fumes in production area



Warning: file(/homepages/23/d294420525/htdocs/cutenews/data/postponed_news.txt) [function.file]: failed to open stream: No such file or directory in /homepages/23/d294420525/htdocs/cutenews/inc/functions.inc.php on line 162
Content Management Powered by CuteNews

© Copyright 2012 Penmann Climatic Systems Ltd. All rights reserved.